Three Phase Power Quality Analyzer Tester with ETCR068B Current Sensor 1000V
$ 1140.48
- Description
- Size Guide
Description
ETCR5000 Power Quality Analyzer's basic function:◆
Transient capture function
Monitoring instantaneous change of power grid voltage current parameters, including the voltage current fluctu-ations, voltage current surge, sag and short supply interruption, temporary overvoltage, impact current and Cur-rent voltage instantaneous distortion. Instruments can store 150 sets of transient waveform at the same time.
◆
Starting current monitoring
Monitoring surge current of line and the startup current when electrical equipment is starting, help to correctly design capacity. Can be display the RMS rising / falling curve In the startup process, the envelope curve of startup current, waveform of 4 channels current and 4 channels voltage. Recording about 100s after trigger, storage the current /voltage instantaneous and waveform curve of each cycle in 100s.
◆
Trend chart recording and storing function
Store all the test parameters of basic test functions (Urms, Uthd, Ucf, Uunb, Hz, Vrms, Vthd, Vcf, Vunb, PST, Arms, Athd, Acf, Aunb, KF,W, VAR, VA, PF, COSφ, TANφ),50 voltage harmonics, 50 current harmonics. And create the trend curve. Record data for a long time according to need(concurrent selection 20 parameters to record data for once every five seconds, you can record about 300 days.).
◆
Alarm function
Set the limit values according to need, monitoring the values whether overshoot, if overshoot will generate an alarm log, such as: voltage, current, unbalance, harmonic ratio, frequency, active power, total harmonic distor-tion. You can configure 40 different alarms, each group can set different monitoring parameters (including 50 harmonics, total of 123 different parameters) and limit values, also can set the shortest time of overshoot. The log can contain up to 12,800 alarms.
◆
Snapshot function
Any screen can be saved (screen snapshot), at the same time automatically records the time and test mode. Such as can save voltage and current waveform, harmonic bar chart, phasor diagram etc. It can save a maximum of 60 screen snapshot.
◆
Communication function
Communicate with computer via USB; Monitoring software can display waveform of power quality analysis, read of the transient waveform, trend chart recording, alarm log, screenshots, and display on the computer.
◆
Setting function
The user can configuration of the time and date, configuration of the screen contrast and brightness, definition of each phase curve colors’.
Choice of type of connection to the net work.
Configuration of the type of the current sensors and voltage ratios.
Select Chinese menu or English menu.
◆
Help menu in Chinese/English
Every stage of operation can press the "help" key to obtain relevant information.
Specification Description
:
▲
Power Supply: Rechargeable lithium battery pack 9.6V, external charger
▲
Power consumption: Current consumption 490mA, battery work 8 hours continuously
▲
Current clamp type: ETCR 068B current clamp: 68mm * 68mm(4PCS), CT size: Ф68mm
▲
Channel number: 4U/4I
▲
Line voltage: 1.0V
~
2000V
▲
Phase voltage: 1.0V
~
1000V
▲
Frequency: 40Hz
~
70Hz
▲
Power parameter: W
,
VA
,
var
,
PF
,
DPF
,
cosφ
,
tanφ
▲
Electrical parameters: Wh
,
varh
,
Vah
▲
Harmonic: Yes, 0 to 50 times
▲
Total harmonic distortion:Yes, 0 to 50 times, each phase
▲
Expert mode: Yes
▲
Transient record group: 150 groups
▲
Voltage flicker: Yes
▲
Start current mode: Yes, 100 seconds
▲
Three phase unbalance: Yes
▲
Record: 300 days (record 20 parameters at the same time, record every 5 seconds, 1 points)
▲
Alarm:40 different types of parameters, the 12800 group alarm log
▲
Phasor diagram display: automatic
▲
Screenshot capacity: 60
▲
Menu language: Chinese and English
▲
Communication interface: USB
▲
Automatic shutdown: The instrument does not shut down automatically when the alarm / trend chart recording / transient capture mode is in progress
;
In other test mode, 15 minutes without key operation, prompt automatic shutdown after 1 minutes.
▲
Test line: Voltage test line 3m, Current clamp 2m
▲
Operating temperature and humidity: -10
℃~
40
℃
;below 80%Rh
▲
Storage temperature and humidity: -10
℃~
60
℃
;below 70%Rh
▲
Input impedance:Test voltage input impedance: 1MΩ
▲
Safety regulation: IEC 61010 1000V Cat III / 600V CAT IV
,
IEC61010-031
,
IEC61326
,
Pollution level 2
▲
Accessory: Host: 1; instrument box: 1; test line: 5 (yellow, green, red, blue, black, 1); Alligator clip: 5; Pen: 5; charger: 1; CD: 1; lithium battery group: 1; 2G memory card: 1;ETCR068B current sensor
:
4