-40%

Power Quality Analyzer Meter Three Phase Power Energy Meter ETCR5000 0.1A~100A

$ 1045.44

Availability: 100 in stock
  • Display mode: LCD color screen, 640dots×480dots,
  • Restocking Fee: No
  • Refund will be given as: Money back or replacement (buyer's choice)
  • Phase Configuration: 3-Phase
  • Frequency: 40Hz~70Hz.
  • MPN: 10369963
  • Return shipping will be paid by: Buyer
  • Expert mode:: Yes
  • Voltage flicker:: Yes
  • Screenshot capacity:: 60
  • Current Measurement Range: 0.10A~100A;
  • Number of channels: 4U/4I.
  • warranty: 1 year
  • Condition: New
  • Item must be returned within: 30 Days
  • Line voltage:: 1.0V~2000V
  • Harmonic:: Yes, 0 to 50 times
  • All returns accepted: Returns Accepted
  • Brand: VTSYIQI
  • Country/Region of Manufacture: China
  • Communication interface:: USB

    Description

    Power Quality Analyzer Meter Three Phase Power Energy Meter ETCR5000 0.1A~100A
    This Power Quality Analyzer comes with 4PCS ETCR040B Clamp Sensors,0.10A~100A Range ,
    if you needs other sensors ,please contact us
    Instruction:
    ETCR5000 Power Quality Analyzer is a comprehensive test instrument carefully developed by our company and specially designed for field test of three phases, multi-functional and intelligent, concise man-machine operation. It is easy to use, large LCD screen display, high resolution, interface in both Chinese and English, shock-proof shell structure and so on. Can simultaneously measure the 4-channel current (ABC three phase and neutral wire current), 4-channel voltage (ABC three-phase voltage and neutral line voltage to ground), the peak value of current voltage,  maximum/minimum value over a period, three-phase imbalance factor, short-time voltage flicker, transformer K factor, active power, reactive power, apparent power, power factor and displacement power factor, active power, reactive power, apparent power, total harmonic distortion and harmonic, etc; Display real-time waveform, harmonic ratio bar charts of current voltage; Dynamically capture instantaneous change of voltage current, monitoring starting current, monitoring the power parameters and generate the alarm list, generate the trend chart for a long time record test data.
    ETCR5000 Power quality analyzer adopt DSP + ARM double processor architecture, DSP is use for data collection and the processing of algorithm, the ARM is use for the communication protocol and the man-machine interface processing; Analog signal acquisition is by 2 pieces AD7655 of ADI company. Resolution for AD7655 is 16 bit and it is 4 channel synchronous sampling. The highest sampling rate can reach 1 MSPS, to ensure the accuracy of the channel and the information integrity, and wouldn’t miss any transient changes in the grid, can more accurate to detect the transient waveform rising and dropping drastically, and waveform instantaneous interrupt; DSP working frequency is over 200 MHZ, to be able to timely monitoring of the power grid and dynamically adjust the sampling frequency to realize synchronization of power frequency and sampling frequency; Using a 5.6 -inch LCD color screen display, a resolution of 640 dots x 480 dots, with different display color difference between the parameters of phase, waveform, vector diagram, harmonic ratio, the user can be more efficient and more intuitive understand the state of power grid parameters. Built-in flash memory can store 60 group of screenshots at the same time, 150 groups of capture transient voltage/current waveform figure, and 12800 groups of alarm list. Starting current detection model can continuously capture starting current waveform for 100 s. Built-in 2G memory card to store the trend curve record, simultaneous recording 20 parameters (can choose according to need) collect data for once every five seconds, trend curve records can be stored for 300 days.
    Product Main Function
    1. This instrument is a comprehensive test instrument of multifunctional, intelligent, man-machine operation simple. Comprehensive analysis and diagnosis all the voltage, current, power, electrical energy, harmonic, phase and other electric parameters
    2. 4 channel current and 4 channel voltage measurement, simultaneously capturing and recording electric parameters and waveform, to provide with all the power quality information for working.
    3. Line voltage:Below 600V
    1. General Specification
    Power supply
    Rechargeable lithium-ion battery packs 9.6V, backup charger.
    Battery Level indicator
    Battery symbol 5 grid   Display power, when the battery level is low, automatically shut down after 1 minute indication
    Working Current
    about 590mA, continuous working 8hours.
    Display mode
    LCD color screen, 640dots × 480dots, 5.6 inches, display field 116mm × 88mm
    Instrument Size
    240mm×170mm×68 mm.
    CT Size
    040Bround jaw current clamp: 35mm×40mm;
    Number of channels
    4 voltages, 4 currents
    Line Voltage
    1.0V~2000V.
    Phase Voltage
    1.0V~1000V.
    Current
    040B current clamp: 0.10A~100A;
    Frequency
    40Hz~70Hz.
    Electricity Energy Parameter
    W, VA, Var, PF, DPF, cosφ, tanφ.
    Energy parameters
    Wh, Varh, Vah.
    Harmonic Wave
    Yes, 0 - 50 times
    Total harmonic distortion
    Yes, 0 - 50 times, each phase
    Expert Mode
    Yes.
    Transient Record Groups
    150 groups
    Voltage Flicker
    Yes
    Start Current Mode
    Yes, 100 seconds
    Three-phases Unbalance
    Yes
    Record
    300 days (record 20 parameters simultaneously, every 5 seconds record 1 point)
    Min/Max Recorded Value
    Yes, the max min value can be measured for a certain time
    Alarm
    40 different types of parameter selection, 12800 group alarm logs
    Peak
    Yes.
    Phasor Diagram Display
    Automatic
    Screenshot Capacity
    60PCS
    Menu language
    English/Chinese.
    Communication Interface
    USB.
    Automatic Shut Down
    In the alarm/trend graph recording/transient capture mode (waiting or in progress), the instrument does not automatically shut down
    In other test modes, there is no button operation within 15 minutes, prompting to automatically shut down after 1 minute.
    Backlight Function
    Yes, suitable for dark places and nighttime use
    Instrument Weight
    Host: 1.6kg (with battery).
    040Bcircle current clamp: 190g×4;
    Test wires and power adapter: 900g;
    Total weight: about 9.2kg (with package).
    Voltage Test Wire Length
    3M
    Current Clamp Wire Length
    2M
    Working Temperature
    -10°C~40°C; below 80%Rh.
    Storage Temperature
    -10°C~60°C; below 70%Rh.
    Input Impedance
    Test voltage input impedance: 1MΩ
    Withstand voltage
    Withstand the sine wave AC voltage of 3700V/50Hz one minute between the instrument line and out shell
    Insulation
    Between instrument line and shell ≥10MΩ.
    Structure
    Double insulation, with insulation shock-proof sheath.
    SuitableSafely Standard
    IEC 61010 1000V Cat III / 600V CAT IV, IEC61010-031, IEC61326, Pollution degree: 2.
    Accessories
    Host: 1PCS; Instrument Bag: 1pcs; Test Cable: 5PCS (yellow, green, red, blue, black); Alligator Clip: 5PCS; Probe: 5PCS; Charger 1PCS; Software CD: 1COPY; 2G Memory Card: 1PCS;Current Clamp ETCR040B 4PCS
    2.Instrument Accuracy  (excluding the current sensor)
    The following data are presented in reference conditions and ideal current sensors
    (completely linear and without phase displacement).
    Measurement Specification
    Range
    Display Resolution
    Max Error of Reference Range
    Frequency
    40Hz~70Hz
    0.01Hz
    ±(0.03)Hz
    Phase Voltage True RMS
    1.0V~1000V
    Min resolution0.1V
    ±(0.5%+5dgt)
    Line Voltage True RMS
    1.0V~2000V
    Min resolution0.1V
    ±(0.5%+5dgt)
    DC Voltage
    1.0V~1000V
    Min resolution0.1V
    ±(1.0%+5dgt)
    Current True RMS
    10mA~3000A
    Min resolution0.1mA
    ±(0.5%+2dgt)
    Phase Voltage Peak
    1.0V~1414V
    Min resolution0.1V
    ±(1.0%+5dgt)
    Line Voltage Peak
    1.0V~2828V
    Min resolution0.1V
    ±(1.0%+5dgt)
    Current Peak
    10mA~4200A
    Min resolution0.1mA
    ±(1.0%+5dgt)
    Peak Factor
    1.00~3.99
    0.01
    ±(1%+2dgt)
    4.00~9.99
    0.01
    ±(5%+2dgt)
    Active Power
    0.000W~9999.9kW
    Min resolution0.001W
    ±(1%+3dgt);Cosφ≥0.8
    ±(1.5%+10dgt);0.2≤Cosφ<0.8
    Reactive power
    Inductive& Capacitive
    0.000VAR~9999.9kVAR
    Min resolution0.001VAR
    ±(1%+3dgt);Sinφ≥0.5
    ±(1.5%+10dgt);0.2≤Sinφ<0.5
    Apparent Power
    0.000VA~9999.9kVA
    Min resolution0.001VA
    ± (1%+3dgt %)
    Power Factor
    -1.000~1.000
    0.001
    ±(1.5%+3dgt);Cosφ≥0.5
    ±(1.5%+10dgt);0.2≤Cosφ<0.5
    Active Energy
    0.000Wh~9999.9MWh
    Min resolution0.001Wh
    ±(1%+3dgt);Cosφ≥0.8
    ±(1.5%+10dgt);0.2≤Cosφ<0.8
    Reactive Energy
    Inductive& Capacitive
    0.000VARh~9999.9MVARh
    Min resolution0.001VARh
    ±(1%+3dgt);Sinφ≥0.5
    ±(1.5%+10dgt);0.2≤Sinφ<0.5
    Apparent Energy
    0.000VAh~9999.9MVAh
    Min resolution0.001VAh
    ±(1%+3dgt)
    Phase Angle
    -179°~180°

    ±(2°)
    Tanφ(VA≥50VA)
    -32.768~32.768
    Min resolution0.001
    ±(1%+5dgt)
    Displacement Power Factor(DPF)
    -1.000~1.000
    0.001
    ±(1%+5dgt)
    HarmonicRatio(Vrms>50V)
    0.0 %~99.9 %
    0.1 %
    ±(1%+5dgt)
    Harmonic Angle(Vrms >50V)
    -179°~180°

    ±(3°)harmonic1~25
    ±(10°)harmonic26~50
    Total Harmonic Rate
    (DF or THD-F)≤50
    0.0 %~99.9 %
    0.1 %
    ±(1%+5dgt)
    Distortion Factor
    (DF or THD-R)≤50
    0.0 %~99.9 %
    0.1 %
    ±(1%+10dgt)
    Transformer K Factor
    1.00~99.99
    0.01
    ±(5 %)
    Three-phase Unbalance
    0.0%~100 %
    0.1 %
    ±(1 %)